Teledyne GFC7000E Manual de usuario Pagina 122

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 265
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 121
Model GFC7000E Instruction Manual Operating Instructions
04584 Rev A1 111
To enable automatic COM port reporting, follow the instruction shown in section 6.12.2.2 then
press:
Edit Data Channel Menu
SETUP X.X
0)
CONC: ATIMER, 1, 900
PREV NEXT INS DEL
EDIT
PRNT
EXIT
Exits to the main
Data Acquisition
menu
SETUP X.X
NAME:CONC
<SET SET> EDIT PRINT EXIT
SETUP X.X
RS-232 REPORT: OFF
<SET SET>
EDIT
PRINT EXIT
ENTR accepts the new
setting and returns to the
previous menu.
EXIT
ignores the new setting
and returns to the previous
menu.
SETUP X.X
RS-232 REPORT: OFF
OFF ENTR EXIT
Toggle key to turn
reporting ON or OFF
Press
SET>
key until…
From the
DATA ACQUISITION
menu
(see Section 6.12.2.2)
6.12.2.8. Compact Report
When enabled, this option avoids unnecessary line breaks on all RS-232 reports. Instead of
reporting each parameter in one channel on a separate line, up to five parameters are reported in
one line.
6.12.2.9. Starting Date
This option allows to specify a starting date for any given channel in case the user wants to start
data acquisition only after a certain time and date. If the Starting Date is in the past, the iDAS
ignores this setting.
6.12.2.10. Disabling/Enabling Data Channels
Data channels can be temporarily disabled, which can reduce the read/write wear on the disk-on-
chip. The ALL_01 channel of the MGFC7000E, for example, is disabled by default.